In the factory, it helps in determining the following :
It is done at site in order to check for abnormalities due to loose connections, broken strands of conductor, high contact resistance in tap changers, highvoltage leads and bushings.
For star connected winding, the resistance shall be measured between the line and neutral terminal.
For star connected auto-transformers the resistance of the HV side is measured between HV terminal and IV terminal, then between IV terminal and the neutral.
For delta connected windings, measurement of winding resistance shall be done between pairs of line terminals. As in delta connection the resistance of individual winding can not be measured separately, the resistance per winding shall be calculated as per the following formula:
The resistance is measured at ambient temperature and then converted toresistance at 75˚C for all practical purposes of comparison with specified design values, previous results and diagnostics.
Winding Resistance at standard temperature of 75° C
Rt = Winding resistance at temperature t.
t = Winding temperature.
Generally transformer windings are immersed in insulation liquid and covered with paper insulation, hence it is impossible to measure the actual winding temperature in a de-energizing transformer at time of transformer windingresistance measurement. An approximation is developed to calculate temperature of winding at that condition, as follows
(Average temperature of insulating oil should be taken 3 to 8 hours after de-energizing transformer and when the difference between top & bottom oil temperatures becomes less than 5° C.)
The resistance can be measured by simple voltmeter ammeter method, Kelvin Bridge meter or automatic winding resistance measurement kit. (ohm meter, preferably 25 Amps kit)
Caution for voltmeter ammeter method: Current shall not exceed 15% of the rated current of the winding. Large values may cause inaccuracy by heating the winding and thereby changing its temperature and resistance.
NB: – Measurement of winding resistance of transformer shall be carried out at each tap.
The transformer winding resistances can be measured by current voltagemethod. In this method of measurement of winding resistance, the test currentis injected to the winding and corresponding voltage drop across the winding is measured.
By applying simple Ohm’s law i.e. Rx = V ⁄ I, one can easily determine the value of resistance.
voltage method of measurement of delta winding resistance” title=”Current Voltage Method of measurement of Delta winding resistance” class=”alignleft”/>
The main principle of bridge method is based on comparing an unknownresistance with a knownresistance. When currents flowing through the arms of bridge circuit become balanced, the reading of galvanometer shows zero deflection that means at balanced condition nocurrent will flow through the galvanometer. Very small value of resistance ( in milli-ohms range) can be accurately measured by Kelvin bridge method whereas for higher value Wheatstone bridge method ofresistance measurement is applied. In bridge method of measurement of winding resistance, the errors is minimized.
The resistancemeasured by Kelvin bridge,
All other steps to be taken during transformer winding resistance measurement in these methods are similar to that of current voltage method of measurement of winding resistance of transformer, except the measuring technique of resistance.
The resistance measured by Wheatstone bridge,