For confirming the specifications and performances of an electrical power transformer it has to go
through numbers of testing procedures. Some tests are done at manufacturer premises before delivering the transformer. Mainly two types of transformer testing are done at manufacturer premises- type test of transformer and routine test of transformer. In addition to that sometransformer tests are also carried out at the consumer site before commissioning and also periodically in regular & emergency basis through out its service life.
Tests done at factory
Tests done at site
To prove that the transformer meets customer’s specifications and design expectations, the transformer has to go through different testing procedures in manufacturer premises. Some transformer tests are carried out for confirming the basic design expectation of that transformer. These tests are done mainly in a prototype unit not in all manufactured units in a lot. Type test of transformer confirms main and basic design criteria of a production lot.
Routine tests of transformer is mainly for confirming operational performance of individual unit in a production lot. Routine tests are carried out on every unit manufactured.
Special tests of transformer is done as per customer requirement to obtain information useful to the user during operation or maintenance of the transformer.
In addition to these, the transformer also goes through some other tests, performed on it, before actual commissioning of the transformer at site. Thetransformer testing performed before commissioning the transformer at site is called pre-commissioning test of transformer. These tests are done to assess the condition of transformer after installation and compare the test results of all the low voltage tests with the factory test reports.
Routine tests of transformer include
That means Routine tests of transformer include all the type tests except temperature rise and vacuum tests. The oil pressure test on transformer to check against leakages past joints and gaskets is included.
Special Tests of transformer include
Transformer winding resistance measurement is carried out to calculate the I2R losses and to calculate winding temperature at the end of a temperature rise test. It is carried out as a type test as well as routine test. It is also done at site to ensure healthiness of a transformer that is to check loose connections, broken strands of conductor, high contact resistance in tap changers, highvoltage leads and bushings etc.
There are different methods for measuring of transformer winding, likewise
NB:- Transformer winding resistance measurement shall be carried out at each tap.
The performance of a transformer largely depends upon perfection of specific turns or voltage ratio of transformer. So transformer ratio test is an essentialtype test of transformer. This test also performed as routine test of transformer. So for ensuring proper performance of electrical powertransformer, voltage and turn ratio test of transformer one of the vital tests.
The procedure of transformer ratio test is simple. We just apply three phase 415 V supply to HV winding, with keeping LV winding open. The we measure the induced voltages at HV and LV terminals of transformer to find out actualvoltage ratio of transformer. We repeat the test for all tap position separately.
Magnetic balance test of transformer is conducted only on three phase transformers to check the imbalance in the magnetic circuit.
In case of auto transformer, magnetic balance test of transformer should be repeated for LV winding also.
There are three limbs side by side in a core of transformer. One phase winding is wound in one limb. The voltage induced in different phases depends upon the respective position of the limb in the core. The voltageinduced in different phases of transformer in respect to neutral terminals given in the table below.
LEFT SIDE PHASE | CENTRAL PHASE | RIGHT SIDE PHASE | |
---|---|---|---|
AN | BN | CN | |
VOLTAGE APPLIED AT LEFT SIDE PHASE | 230 V | 180 V | 50 V |
VOLTAGE APPLIED AT CENTRAL PHASE | 115 V | 230 V | 115 V |
VOLTAGE APPLIED AT RIGHT SIDE PHASE | 50 V | 180 V | 230 V |
Magnetizing current test of transformer is performed to locate defects in the magnetic core structure, shifting of windings, failure in turn to turn insulation or problem in tap changers. These conditions change the effective reluctance of the magnetic circuit, thus affecting the currentrequired to establish flux in the core.
Generally there are two similar higher readings on two outer limb phases on transformer core and one lower reading on the centre limb phase, in case of three phase transformers. An agreement to within 30% of the measured exciting current with the previous test is usually considered satisfactory. If the measured exciting current value is 50 times higher than the value measured during factory test, there is likelihood of a fault in the winding which needs further analysis.
Caution: This magnetizing current test of transformer is to be carried out before DC resistance measurement.
In three phase transformer, it is essential to carry out a vector group test of transformer. Proper vector grouping in a transformer is an essential criteria for parallel operation of transformers.
There are several internal connection of three phase transformer are available in market. These several connections gives various magnitudes and phase of the secondary voltage; the magnitude can be adjusted for parallel operation by suitable choice of turn ratio, but the phase divergence can not be compensated. So we have to choose those transformer for parallel operation whose phase sequence and phase divergence are same. All the transformers with same vector ground have same phase sequence and phase divergence between primary and secondary. So before procuring one electrical power transformer, one should ensure the vector group of the transformer, whether it will be matched with his or her existing system or not. The vector group test of transformer confirms his or her requirements.
Insulation resistance test of transformer is essential type test. This test is carried out to ensure the healthiness of over all insulation system of an electrical power transformer.
NB : It is unnecessary to perform insulation resistance test of transformer per phase wise in three phase transformer. IR values are taken between the windings collectively as because all the windings on HV side are internally connected together to form either star or delta and also all the windings on LV side are internally connected together to form either star or delta.
Measurements are to be taken as follows:
Oil temperature should be noted at the time of insulation resistancetest of transformer. Since the IR value of transformer insulating oil may vary with temperature.
IR values to be recorded at intervals of 15 seconds, 1 minute and 10 minutes.
With the duration of application of voltage, IR value increases. The increase in IR is an indication of dryness of insulation.
Absorption coefficient = 1 minute value/ 15 secs. value.
Polarization index = 10 minutes value / 1 minute value.
The induced voltage test of transformer is intended to check the inter turn and line end insulation as well as main insulation to earth and between windings-
The test is successful if no break down occurs at full test voltage during test.
Temperature rise test of transformer is included in type test of transformer. In this test we check whether the temperature rising limit of the transformer winding and oil as per specification or not.
In this type test of transformer, we have to check oil temperature rise as well as winding temperature rise limits of an electrical transformer.